Thursday, December 6, 2018

Motor Control Starter Basics (Direct-On-line)


The term "Motor Control Starter" is actually confusing for some people. Technically, the main purpose ng motor starter is not to start the motor, but to let motor start and run without damage.
The term starter is based only on the overload relay that is used to protect the motor from starting current.

In simplest form, motor control starter can be seen in a Direct-On-Line circuit which is composed of MCCB, Magnetic Contactor and Overload Relay.

1)  Molded Case Circuit Breaker (MCCB) - Ang circuit breaker ay may tatlong functions: (a) Isolator, (b) Proteksyon a circuit sa Overload, Grounding at Short Circuit (c) Switching purposes. Sa Control Panel, nasa itaas ang breaker dahil ito ang unang main protection na kakailanganin sa motor. In case may exposed wires na nagcause ng electrical leak o short circuit, agad agad itong magtritrip.

 Kadalasan din itong ginagamit para mahiwalay ang power supply sa motor sakali may preventive or corrective maintenance na gagawin.

2)  Magnetic Contactor  - Ang magnetic contactor ay isang klase ng relay na ginagamit para sa frequent switching ng isang circuit.  Para lang itong "pinalaki na auxiliary relay" - may electromagnectic coil at nagproprovide ng karagdagang contacts sa circuit para sa ON-OFF mode.

Importante ito sa Motor Control.  As per definition ng mga nauna kong articles, ang relay ay power device na kayang kontrolin ang mas mataas na boltahe. Sa concept ng magnetic contactor, halimbawa, ang may 24VAC coil na contactor ay pwedeng kontrolin ang mas mataas na 220 VAC switched circuit. Dahil sa magnetic contactor,  naging posible din kabitan ng ibang mas maliliit na devices para sa motor.  (For instance, ikonekta lang sa contactor ang ilang auxiliary relays at pwede nang lagyan ng karagdagang pushbuttons, pilot led lights at selector switches)

Ang magnetic contactor ay gamit para sa Manual Control or Automatic Control System.
Paano naman ito gagana? Simple lang. Ang Contactor sa Direct-on-line ay nasa Normally Open (N.O) na position. Pag dadaan ang current sa coil (or maenergize ang coil sa technical term), ang contacts na magkahiwalay ay magdidikit, magcloclose ang circuit at mag-Start ang motor.


3) Overload Relay - Sa baba ng magnetic contactor ang overload relay. Ipinapares  ito sa magnetic contactor pasa sa Overload Protection. Ang OL Relay ay hinahayan ang mga short current overloads na dumadaan sa motor sa unang andar nito ngunit automatic na nagtritrip pag naging tuloy-tuloy ang overload current.

Sa principle ng magnetic induction, ang isang motor ay kailangan ng malakas na current para maset up ang electromagnetic field. Ibig sabihin, isang malakas sa sipa ng kuryente muna, para mapaandar ang motor. Ang disadvantage dito, pag parati itong mangyayari, madaling mag-iinit ang motor na pwede ikasira kaagad nito.

Ang overload relay ang solusyon sa isyu ng high starting torque. Dahil dito, naging posibleng gamitin ang motor nang hindi nasisira kaagad. Naiiwasan nating maoverheat ang motor. In short, iwas sunog sa motor windings.


Additional notes:
  • Magnetic Contactor + Overload Relay = Motor Starter. Ang simpleng motor starter ay kailangan lang ng dalawang devices.  Kaya lang, walang kakayahan ang magnetic contactor na magcause ng power intteruption sa tuwing may short circuit. Dito pumapasok ang MCCB.
  •  Molded Case Circuit Breaker + (Magnetic Contactor + Overload Relay) = Combination Magnetic Starter  



Saturday, November 10, 2018

KAIC, The Unpopular

KILOAMPERE CAPACITY RATING  o KAIC, sino ba ang nakakaalam nun? Kahit ang mga estudyante ng engineering ay kalimitan ding di alam kung bakit kailangan ito. 

Kung mapapansin mo, ang protective devices na karamihang makikita sa mga electrical plans ay mayroong continuous current rating (ang karaniwang consumption ng load habang ginagamit ang kuryente. Pero ang KAIC, kadalasang di nababanggit.

Ang KAIC ngayon ang most taken for granted na component sa system design.

Ang circuit breaker ay mayroong tatlong mahahalagang components - ang continuous current rating, ang voltage rating at ang pangatlo, ang interrupting capacity rating. Ang KAIC ang maximum tolerable amount ng current sa tuwing magtritrip ang circuit breaker nang hindi ito nasisira. Mas mababang KAIC kapag sa mga residential lang dahil mas magagaan ang mga load. Mas mataas naman sa mga industrial kung saan nandoon karamihan ang mga malalaking motor.

Example:
    30 AT, 2P, 10 KAIC @220 V  MCB  (para sa main breaker ng isang lighting panel)
  250AT, 3P, 25 KAIC @220 V MCCB (para sa isolator ng VFD o inverter)  

Sa mga bahay, dahil lightings at power circuit lang, karaniwang 7-10 KAIC.  15 KAIC pataas naman pag mga mabibigat ng load. 

Pwedeng ding masabi na ang KAIC ay aftershock component. Kapag hindi nakayanan ng breaker ang fault current, pwede itong madisintegrate.  Kung ang circuit breaker ay nandoon para protektahan ang ating mga linya ng kuryente, kailangan din nitong protektahan ang mismong sarili nya.

Ang nasa babang larawang ay Medium Voltage Circuit Breaker na undersized sa KAIC. Nagkaroon lang ng fault ay sumabog na ang breaker at nasunog.









Malay sa relay na yan. =( A BIG NO NO. (part 2)

Anong mangyayari pag naconnect ang isang AC relay 

sa DC?


Ang isang AC relay coil has both inductance and resistance limiting the current.
Generally, ang AC relay ay nakadesign nang may mas mataas ng current kesa sa DC
(kasi mas less efficient ang AC). Pag naikabit ito sa DC at hindi sa AC, magkakaroon ng mas
mataas na current pa rin. The relay would operate properly (for a while) but would eventually
fail due to the coil overheating. Depending on ambient temperature and the specific relay,
failure could occur in minutes, or might take years.

What is a Motor Control?

Ano ba ang motor control? A question that has no simple answer?? well, it is not.. however, mysterious, complicated subject that some people believe it to be.


As what the word control means, it governs or regulates. Pag sinasabing motor control, ang pinag-uusapan ay paano magmanage ng machines o motor, like starting and stopping, selecting forward or reverse rotation ng motor, limiting of the speed and motor


protection. kasi ang klase ng MOTOR CONTROL: 1) manual para sa mga simpleng motor at (2) automatic para sa mas efficient at di masyado kailangan ng manpower na operation.



Sa basic na manual controller, ang pwede nating makita ay dalawang pushbuttons, isang START PUSHBUTTON at isang STOP PUSHBUTTON. Meron ding overload protection para maiwasang masira at magkaroon ng aksidente. I think ang pinakamagandang example dito ay ang welding machines. ;)


Ang automatic motor controller naman ay ginagamit para sa mabilisang produksyon, more accurate at more efficient na operations. Well kung mas mura magpakabit ng manual controllers, ang automatic system naman ay di hamak na nagiging mura pagdating sa flexibility, maintenance at operational costs.

The Famous Unknown Neutral Wire

Ano ba ang neutral wire? Well, madali pong masagot yun ng isang electrical student. Neutral wire is a wire used for grounding na pwede ding magdala ng current and is coded with a "WHITE COLOR"

Ngunit paano ba maeexplain ng isang electrical student or grad ang neutral wire sa ibang tao. Well, simple lang. =) Ang neutral wire ay nakakonekta sa SAFETY GROUND sa SERVICE ENTRANCE o abang kaya pag kinukuhan ng boltahe ang neutral at ground ay ala talagang makukuha kasi magkadugtong silang dalawa.

Ngunit bakit ba tayo gumagamit ng neutral wire??? =) sa grounding lang ba to?

Ginagamit ang nuetral wire to ALLOW the three-phase system to use a higher voltage while still supporting lower-voltage single-phase appliances.

Halimbawa, yung main supply natin na three-phase ay 400 V, at meron tayong load na kailangan sa 240 V lang ( square root of 3 para sa line-to-neutral na voltage). Magagamit natin ang neutral wire dito. Ang kuryente kasi ay parang tubig. It needs a complete circuit to flow


Ganito kasi yun, kung 3-phase load ang ikakabit, tallong wire ang meron tayo. Hindi na natin masyadong kailangan ng neutral wire, kasi ang tatlong wire ay ikokonekta sa tatlong linya, LINE A, LINE B at LINE C. Ang magiging voltage ay phase-to-phase. Kaya kung 440 V ang boltahe mo sa MAIN SUPPLY, 440 V din ang voltage sa three-phase na load. Ngunit para sa single phase na load, dalawang wire lang ang ikakabit sa supply. Isa pwedeng ikabit sa A, B o C (hot wire) at ang isa naman ay ikakabit sa neutral.


Ang nuetral wire ang maghahatid ng return current sa electrical company o sa source ng kuryente para makompleto ang circuit. =) At tandaan, mas mababa na ang voltage nito.


Pero what if lahat ng load ay three-phase din. Bat kakailanganin natin ng neutral wire?????????
Well, nangyayari to sa four-wire at five-wire system. Mas nakakaintriga sa five-wire system. May tatlong hot wire na, may grounding wire din, may NEUTRAL WIRE PA. Nakakalito? Hmmnn.

As long as the 3 loads (for each of the 3 phases) are perfectly balanced, there is no need for a neutral. Kayang kaya dalhin yun ng tatlong linya. Pero, almost all the time, lalo na sa mga residential, ang balanced load na design ng mga engineer, di din nangyayari. Hindi kasi lahat ng appliances at nagaganit. Right??

And worse, what if isang linya lang ang gumana. Let's say, yung line A lang na loads ang magagamit, samantalang ala sa line B at line C. Ang unbalanced current na yun, ay best suited na dalhin ng fourth wire, at yun ANG NUETRAL WIRE. ;)

The Heroes..

Mga Tao sa Likod ng ating Electrical Convenience Ngayon

  • Ang pinakaunang electrical engineer na nabuhay noong 17 th century ay si WILLIAM GILBERT, isang scientist at natural philosoper. Sabi nga , siya ang father ng electricity at magnetism. 
  • William concluded that the Earth was itself magnetic and that this was the reason compasses point north (previously, some believed that it was the pole star (Polaris) or a large magnetic island on the north pole that attracted the compass). He was the first to argue, correctly, that the centre of the Earth was iron, and he considered an important and related property of magnets was that they can be cut, each forming a new magnet with north and south poles.
  • In his book, he also studied static electricity using amber; amber is called elektron in Greek, so Gilbert decided to call its effect the electric force. Sya ang gumawa ng unang electroscope, gamit ang isang karayom.
  • Ang pinakaunang tao naman na gumamit ng word na ELECTRICITY naman ay si Sir Thomas Browne, isang manunulat, Ang salita ay galing sa LATIN word na electricus, meaning "like amber". 
  • Sinundan si William Gilbert ni Alesandro Volta, isang physicist, na syang nakagawa ng BATTERY o ng unang electric cell. Sya ang nakadiskubre sa electric capaitance (C), sa charge (Q) at sa electric potential (V). ( Q = CV)
  • Di rin pwedeng mawala sa listahan si ginawa ni Benjamin Franklin sa kanyang researches. Sya lang ang bukod tanging nagpalipad ng saranggola habang umuuln ng malakas at nagpatunay na ang kidlat ay isang klase ng kuryente. Dun din pumasok sa kanyang mga pagsasaliksik ang teorya sa grounding at marami pang iba. 
  • Pagkatapos sa kanya ay si George Ohm, isang German physicist at guro, na sya namang nagexplain ng pagkakaiba ng electric current at potential difference sa isang conductor na nagsimula ng electrical circuit analysis. Sikat ang kanyang OHMS LAW V = IR, at mula sa kanyang mga nagawang principle, ay ang applications na ng electric current.
  • Andyan din si Michael Faraday, ang nag-imbento ng electric motor. Sa kanya nagsimula ang electromagnetic induction. Isang chemist at physicist, pinaghalong nya ang dalawang science at nabuo ang electrochermistry. 
  • Si Nikola Tesla naman kung saan pinangalan ang unit ng electromagnetic flux, ang "tesla", hehe. Sya naman ay nagconcentrate sa electromechanical engineering. Sa AC machines at sa polyphase, panalong panalo tayo sa kanyang mga ibinahaging kaalaman. Si Tesla ang itinuturing na isa sa may pinakamalaking naibahagi sa electrical technology ngayon. Ang Alternating Current (AC) circuits na syang ginagamit natin ngayon sa power generation and transmission. Ang kuryente na nanggagaling sa ating utility companies ay AC at lahat ng mga machines ngayon ay dito nakabase ang design.
  • Si Thomas Edison naman ang pinakapaborito ko. Sa kanya nakadiskobre ang Direct Current (DC) circuits kung saan nakabase ang design ng batteries. Siya din ang nakaimbento ng motion-picture camera, at ang nagdala ng liwanag sa ating kabahayan sa kanyang naimbentong "electric bulb". At an early age, Thomas Edison developed a hearing impairment, pero di ito naging hadlang para di sya magtagumpay. Napunta sila sa Michigan ng kanyang pamilya at dun ay nagtinda sya ng mga candy, newspaper at mga gulay. At dahil sa likas na madiskarte, ang maliit na businessman ay swerteng napasok sa General Electric (GE), isang malaking company. Quotable quote: We will make electricity so cheap that only the rich will burn candles." =)

Tuesday, November 6, 2018

Mainit na Linya o Hot Wire

Pano kapag ang isang linya ay mas mainit kaysa sa iba?

1) Una tingnan muna kung unbalanced ang circuit. Isa isang tingnan ang amperaha at kung mas mataas ito kaysa sa iba.

2) Tingnan kung maluwag ang terminal. Kapag maluwag kasi ang dinadaluyan ng kuryente, chances are, exposed ang kable, may tendency magleak ang current, kakalat ito, hindi masyadong nakokontrol ang circuit at mas iinit ang kable.

3) Idouble check baka may sunog na part. Sakaling naputulan na ang kable dati pa, nung nasunog ito, siguraduhing lahat ng sunog ay wala na dun. Kahit gaano kaunti ang sunog pag naroon pa rin sa circuit, maaaring magdulot pa rin ito ng problema.

Note: pag may sunog na area sa kable, di nakakadaloy nang maayos ang kuryente, nagtatambak (natratrapik) sa isang lugar kaya umiinit. Katagalan, ang kaunting sunog ay lalaki nang lalaki hanggang sa bumigay ang kable. Lalo pa kung ito ay nasa dulo, masusunog ang terminal sa breaker. 

Makukulay na Wires

Kapag nagtritrip ang main breaker,  ang pagcheck sa fuse ay isa sa pinakaunang dapat gawin.

Pagkatapos ay gumamit ng neon tester o screwdriver na umiilaw pag itinatapat sa wiring 
na live para malaman kung may kuryente o wala.

Para maiwasan ang anumang pagkakamali, pwede ring tingnan ang kulay ng mga wire.

Sa electrical, karamihan ay COLOR CODED. 

1) White wires - ang mga to ay karaniwang nakakonekta sa mga terminal ng screws at 
receptacles.

2) Black wires-  ang mga "ultimate hot wires" kung tawagin. Ang mga ito ang may 
dala ng power supply papuntang outlet o switch. Note: Ito ay hindi kailanman 
ginagamit para sa ground o neutral connection.  


3) Red wires - Pwede ding maging "hot wires". In 220-volt installations, the red wire is usually connected sa Control Circuit. 

4) 
Blue and yellow wires - "Hot wires" pa rin ang mga ito, ngunit karaniwang ginagamit 
papuntang conduits para madaling matrace ang wiring. Blue is usually used for para sa 
mga circuits na malalayo at kalimitan din sa mga three way at four way switches na or 
as switch legs in lights and fans.

5) Yellow wires -  Karaniwan nakakonekta sa mga switches 

5) Green - Ground wires. For electrical appliance safety. 

Madaling malaman ang mga dapat at hindi sa electrical wiring. Sa bawat kulay na 
meron ang isang wire, ito'y nananatiling palatandaan kung delikado ito o hindi 
at kung saan ito nakaconnect sa isang circuito.

Monday, November 5, 2018

Solar Powered Hot Water System

 Halimbawa raw maaraw at nilagay natin ang isang bote na may tubig sa tapat ng bintana at iniwan dun ng ilang oras. Pagkabalik natin ay mapapansin natin na ang bote ay madaling uminit. Mas maraming laman na tubig ang bote, mas mainit at mas maraming bote na ilagay sa bintana, mas lalo pang maraming init ang naiipon.

  Ang solar panel ay ganito maiisasalarawan. Sakaling subukan na lagyan ng butas ang mga bote sa magkabilang dulo, lagyan ng PIPE kung 
saan pwede na pagdaluyan ng tubig  at maikonekta sa ating water supply system. Kabitan lang ng WATER TANK at PUMP para tuloy tuloy ang takbo ng tubig sa buong kabahayan, meron ka na din simpleng SOLAR POWERED HOT WATER SYSTEM.

Thursday, November 1, 2018

Hybrid Power Systems (Solar + Wind Energy)


To quote Philippine Star (dated May 3, 2011), " ___'s most recent green initiative is the utilization of a solar-powered air-conditioning system". One of today’s fast-growing green trends, solar-powered air-conditioning systems merge economics, advanced technology, and ecology, and harness heat from the sun, a clean, consistent, and safe power source

Ang ginamit ==> Hybrid solar and wind electric system.

Paano it gumagana?


Obviously, ang solar panels ay gumagana sa gabi, pero dito naman pumapalo ang hangin. O kung tirik na tirik ang araw at wala masyado ang hangin, may mapagkukunan pa rin tayo ng enerhiya.

Dito sa Pilipinas, ang hangin ay malakas tuwing tag-ulan habang hindi masyado ang araw, samantalang mahina it sa tag-init habgang malakas ang araw. Sa ganitong paraan, ang kombinasyon ng wind-generated at solar-generated system ay isa sa pinakamagandang naimbento sa panahon ng makabagong teknolohiya.


Dahil sa pwede itong makapagbigay ng malakas na energy, ang sistemang ito ay magagamit sa magkakaibang panahon at sulit sa mga building owners.

Depende sa design, ang hybrid system ay pwede ikonkta sa MERALCO sakaling kailanganin ito o nakakonekta sa generator para sa back up.

FYI: Disconnected Neutral (Open neutral)" fault condition


Paano pag ang NEUTRAL WIRE ay energized pero hindi nagtritrip ang circuit breaker?

Ito'y nangyayari lamang KAPAG ang neutral wire ay hindi nakakabit sa main power supply samantalang ang Line or "hot wire" para sa curcuit are konektado pa rin sa panel, at ang mga appliances are nakaplug sa mga outlet.

Pag hindi konektado sa main supply, dadaaanan pa din ito ng kuryente sa twing umaandar ang mga electrical loads natin at dahil kailangan natural sa kuryente ang maghanap ng path to earth, delikado sa tao sa mahawakan ang neutral wire na tulad nito.


Walang ORDINARYONG circuit breaker sa OPEN NEUTRAL FAULT CONDITION ang magtrireip o MAGSHUSHUTDOWN kasi ang line-to-neutral na current ay HINDI GANUN KATAAS.

In that situation, if you put a voltage indicator, such as a test screwdriver with a neon lamp onto the Neutral wire it will glow just as if it was Live, because it is being fed with a very small current coming from the Live supply via the plugged-in appliance(s) to the Neutral wire.

If you unplug all appliances, lights and whatever else may be connected to the circuit, the Neutral will no longer seem to be Live because there is no longer any path from it to the Live supply.


Even if there is a GFCI or an RCD in the circuit that too is unlikely to trip in this situation because the test current is so small and is of the same size - an equal current flow - in both the Live and the Neutral wires.

A "Disconnected Neutral" fault condition is VERY UNSAFE because somebody who does not know about the danger could easily touch the Neutral wire and get a bad shock whilst trying to find out why no appliances work when they are plugged into a circuit that actually has such a "Disconnected Neutral" fault condition.

Warning : Disconnected Neutral



Ang disconnected neutral at tinatawag ding open neutral fault condition. Ito'y nangyayari pag nadisconnect ang neutral wire sa main power supply
PERO nakakonekta pa rin ang hot wire sa panel at habang umaandar ang electrical loads, katakot takot din ang pwede mangyari sa ating mga appliances .
Subukan mong gamitin ng test screwdriver na merong neon lamp sa neitral wire, ang lamp indicator ay iilaw pa parang live wire na din ang neutral wire. At bakit nagyayari ito???
Actually merong napakaliit na current na dumadaan sa neutral wire galing sa Live supply via the plugged-in appliance(s) to the Neutral wire.
If you unplug all appliances, lights and whatever else may be connected to the circuit, ang neutral wire ay ala na din current because there is no longer any path from it to the Live supply. Di din magtritrip ang circuit breaker kasi ang current na dumadaan mula sa live via sa ating mga load papunta sa neutral ay napakaliit para madetect ng ating circuit breaker.

A "Disconnected Neutral" fault condition ay NAPAKA UNSAFE kasi maaaring tayong maaksidente dito at makuryente while trying to find out 
why no appliances work samantalang nakaplug naman ito sa outlet.



Power System

POWER SYSTEM

Ang power distribution ngayon at ang mga control systems are far more complex kesa sa dati.
They are designed with MULTIPLE LEVEL of redundancy, na ginagamitan ng PLC, para sa back up at emergency at inputs para sa multiple building systems.
Una, ano nga ba ang PLC?
Ito’y isang digital computer used for automation of electromechanical assembly lines, amusement rides, or lighting fixtures. processes, such as control of machinery on factory
At ano ano ba ang mga pwede mangyari in case ng isang EMERGENCY or power outage sa distribution system????????
Well, pwede magkagulo!! Below is an example of how electricians react to emergencies. Pitong oras silang nagkaroon ng isyu sa kuryente na pwede sanang masugpo ng dalawampung minuto kung natrain lang ang mga electricians ng dapat nilang gawin.







10:30 A.M.
Biglang nawala ang kuryente.
Dahil merong anim na UTILITY LINES para sa facility, mula sa iba’t ibang substation, alang back up na generator na nakainstall. Napag-alaman ng facilities manager na APAT na circuit breaker ang open. Pano nangyari ito????
The MAIN TIE AUTO-TRANSFER SYSTEM is designed for open transition transfers. Ang mga relays ang nagsisilbing sensor para sa LINE VOLTAGE at nakikipagcommunicate sa ating PLC.
Ang PLC naman ang utak ng control system na nabubukas ng MAIN o ng BREAKER TIE para marestore ang service to the load.
Ang dalawang natitirang power source ay ang emergency lines na lang.

Step 1) Both services ay ginawang MANUAL MODE ng mga electrician in attempt na maclose yung mga ito manually. One at a time, the electricians tried to close them,pero nagtritrip agad ang mga ito.Ibig sabhin, me problema nga… tsk tsk.
10:50 A.M.
Step 2) A second attempt succeeds, and one main in each service is closed. Power is restored to part of the facility. Kaya lang, hindi nacloclose ang B main breaker. (So ito siguro ang me problema.)
Step 3) Having already closed the TIE at MAIN A, the electricians tried closing again B main breaker.Ang resulta, both the TIE BREAKER at ang B MAIN BREAKER ay nagtrip ulit at nagopen and circuit. The maintenance manager reclosed the B-main at this time, it REMAINED CLOSE. (whew! hehe)
Step 4)

With power partially restored, nagdecide ang maintenance crew na hayaan na lang muna ang power system at magpatulong sa iba. Dalawang contractor electrician na nag-install ng mga ito ang pumunta doon.
3:30 P.M.
Step 5) The contractor's electricians looked over schematic drawings for more than two hours. Kaya lang, narealize din nila na din nila kaya ang problema. Tinawagan nila ang Manufacturer mismo ng circuit breakers at sinabihan pupunatahn sila dalawang oras pagkatapos tumawag .
5:15 P.M.
The Square D Services representative arrives.

5:25 P.M.
All power is restored and production resumes.
In this distribution system, we have the HIGH VOLTAGE SWITCH na nagsusuply ng 13.8 kV
galing sa utility company. Pwede itong 150 ampere delta connected
power to two 2000 kVA 

dry-type transformer.
At ano nga ba ang dry transformer????

Well, ganito yun.
Ang Dry-Type Transformers ay ginagamit sa
loob at labas ng isang building, eskwelahan, ospital,
commercial building at iba pang lugar na
nangangailangan ng dependable power supply.
Dry-Type Transformers are available for voltages
up through 34.5 kV (although the most common
upper limit is 15) and KVA ratings up through 10,000 (with 5000
as the usual limit). Ang dry type tranformer ay gumagamit ng hangin
para mapanaliting tuyo, lowering health and environmentally
concerns.
Ang dry type transformer naman ay connected sa MAIN TIE CIRCUIT BREAKERS.
Gamit ang PLC, nagkakaroon tayo ng automatic operation para makasigurong
magkakaroon pa rin ng kuryente ang BUONG SWITCHBOARD LOAD kahit ang
isang main supply ay mawalan.

Malay sa Relay na Yan

Malay sa relay na yan. =( A BIG NO NO. (part 2)


We can say that a relay is A SPECIAL KIND of switch.


Here are two examples kung bakit kailangan natin ng relay.


On the upper part is a diagram for automobile circuit.

Pag naka-on ang ignition key ng sasakyan, it allows electricity to flow to the starter solenoid ( yun ang relay) which then connects the battery to the starter motor.
So why do we need the "middle man" relay? Pwede ba nating e-eliminate na lang ito at iconnect ang ignition wires sa +battery terminal at yung isang wire sa motor starter naman?
The important point here is that the electromagmet is using a small amount of current to control a large amount of current to the starter motor. (Remember that the electromagnet and the switch areNOT connected electrically).

Have you noticed that a
ll of the wires (except the ignition wires) are purposely drawn with thick lines? That's because some circuits (like the starter) require tremendous amount of current. (kaya kailangan din ng mas malaking kable).

(If you look at an automobile's battery cables, you will notice they are quite thick.)

Pag maliliit na wire ang ginamit natin, di nito kakayanin ng insulation nya ang mataas na current, kaya masusunog ito, at uusok.
We do have a second choice. Pwede tayong gumamit ng malalaking kable mula sa battery gamit
ang heavy duty ignition switch. However, do yo
u think it would be easy to squeeze cables into thesteering column and squeeze in a heavy duty switch too?
BURGLAR ALARM SYSTEM

Referring to the diagram, let's trace theelectrical flow. 

Kung makikita nyo, mula pt. V2, pupunta sa "C". Mula sa negative battery terminal, pupunta sa V1, tapos sa V2, at dahil tuloy tuloy ang alarm loop, pupunta sa "C" at pagkatapos ay sa positive battery terminal na. Sa circuit loop na 'to, dadaloy ang current sa electromagnet causing the common terminal to switch contact mula "C" patungo sa "B" At dahil walang contact sa A, the siren will not make any SOUND.

Pwedeng lagyan ng isa o mas maraming magnetic switch in series sa alarm loop para magkaroon ng warning signal o alarm sound. Kaya lang, ang mangyayari dito, tuloy-tuloy nga ang kuryente mula pt "C" to pt. "A" hanggang sa siren, NGUNIT HINDI sa electromagnet.

Alarm Circuit 1 does suffer from one serious flaw. Can you see what it is? Pag nareconnect ulit ang alarm loop, madidisconnect lang ang siren. This is a VERY IMPRACTICAL WAY AND NOT RECOMMENDED TO ANY ALARM SYSTEM. The siren goes off! Kung nabuksan ng isang magnanakaw ang pintong me magnetic switch nang pwersahan, sasarhan lang nito ulit ang pinto at di na tutunog ang siren.

Para maging efficient sa tao, kinakailangan natin ng isang device na pagproprovide ng additional contacts na mag-aallow ng isang circuit na gumana habang ang isang circuit ay putol. At yun ang nagagawa ng transfer mechanism ng common contact ng isang relay. =)

Frequently Asked Questions: Powerline

Frequently asked questions, powerline!!

1) Are power lines insulated?
Kala ng karamihan sa atin, ang power lines o yung malalaking kable na galing sa utility company papunta sa mga poste papunta sa mga consumers have INSULATION MATERIAL around them kagaya ng mga electric cords ng mga applicances.

FYI, ang high voltage na linya ay HINDI INSULATED.
 The protective covering around it is not an insulation. It only PROTECTS THE LINE FROM WEATHER CHANGES.

Ang mga appliances natin ay gumagamit ng 110 o 220 Volts.
At that leve
l, insulation material is practical. But at 7,200 Volts o higit pa, ang insulation material ay masusunog lang dahil di nito kakayanin ang mataas na kuryente, right??

And if the material was substantial enough to handle the HIGH VOLTAGE, it would be too expensive, TOO THICK and TOO HEAVY to USE.

2) 
Why can birds sit on power lines without being hurt, when it would kill me to touch that same line?


Ang kuryente daw ay tamad, By nature, hinahanap ng kuryente ang PINAKAMADALING PATH papunta sa ground. 

When a bird lands on the line, 
her body becomes charged--for the moment, it's at the same voltage as the wire.

Kaya lang, di sya makukuryente kasi mas pipiliin ng current na dumiretso na lang sa copper wire ng power line kaysa pumasok o mag-detour sa katawan ng ibon na less yung conductivity.

Makukuryente lang ang isang ibon KUNG ang isang paa nya ay nasa conductor at ang ISA ay nasa isang path to ground.

Kaya kung ang isang squirrel ang dumaan sa power line, makakasurvive sya PERO makurkuryente din the moment na mahawakan o maapakan nya ang (grounded) transformer na nasa dulo ng wire.

Ngayon, if in any case, ang isang tao ay umakyat sa puno at humawak sa power line, madaling makakapasok ang kuryente sa kanya, papunta sa puno, papunta sa ground.
=S



Electrical Applicances in Flood

Electrical Appliances in flood

Readiness, Response and Recovery.


Emergency 101


Before entering a home after a flood, be sure that the electricity has been
completely shut off at the panel. If you are not certain how this is done, get a licensed electrician or authorized service person to do this for
you. 


Pag meron pa ding tubig sa paligid ng appliances, iwasang pumunta malapit dito lalo na't di sigurado kung nakashut off ang appliances. Pweding masave ang appliances pero kailangan munang PATUYUIN ang mga ito bago gumawa ng hakbang.

SAFETY MEASURE:
NEVER allow the connection between the machine's power cord and the extension cord to lie in water.ELECTRIC CIRCUIT BREAKERS AND FUSES can malfunction when water and silt get inside. Discard ALL circuit breakers and fuses that have been submerged.


Appliances in flood can be classified into two:
a) submerged in water
b) just wet by rainwater

Appliances submerged in water are often NOT REPAIRABLE but the appliances that have been saved and not flooded are often REPAIRABLE.

Water, especially dirty floodwater, na puno ng putik, causes many problems (lalo na pag nakapasok ang mga ito sa motor windings, electrical contacts at mga switches). Pwedeng kalawangin ang mga ito at di na gumana. 

Kung nakapasok naman ang mga ito sa insulation, ang mga appliances na mga heater o cooler gaya ng electrical ranges, freezers or ref ay pwedeng di na rin gumana nang maayos at magkaroon ng masangsang na amoy.

Appliances damaged by water can sometimes be made functional, but they will likely have a shortened life expectancy. Depende kung gaano katagal ang mga appliances bago sila nabasa, ang buhay ng mga appliances ay umiikli.. 

1) How to CLEAN APPLIANCES 

Never hose them down!! Ang mga appliances ay di gamitan ng hose ng tubig para malinis kaagad. Keep in mind that electricity and water should not mix..

Pwedeng gumamit nalang ng basang pamunas na madaling matuyo para alisin ang dumi sa appliances. Pwede ding gumamit ng electric fan to increase airflow.
You can also try using CONTACT CLEANER ( solvent na iniispray at madaling mag-evaporate gaya ng isoprophyl alcohol ) para sa mga contacts ng switches.


2) GETTING RID OF ODOR

If an odor persists, wash with a solution 
All we need are the following:
isang kutsarita ng baking soda 
isang 1/4 gallon ng tubig
isang cup ng suka 


Pwede ding isang cup ng household ammonia kada isang galon ng tubig. 

Ceiling Fan Ngayong Summer

Ceiling Fan Ngayong Summer



Fans don't make the air cooler!
 
They work by blowing away the envelope of warm air that surrounds your body.
As a living creature, you generate heat. A lot of it. As that heat slowly radiates away from your body, it creates a pocket of hot air that surrounds you. It's like you're being insulated by an invisible bubble of heat. What fans do is to push that hot surrounding air out of the way.
This is why blowing on hot food cools it off. It's not that your breath is especially cool, it's that you're blowing the heat off the food.
If you're sweating at all then the fan also cools you by speeding up the evaporation.
So now that you know that fans don't make the air cooler, you can see that there's no advantage to leaving the fan on when you leave the room. Fans don't lower the temperature in the room at all.
By the way, a typical 36" / 48" / 52" ceiling fan uses about 55 / 75 / 90 watts of electricity respectively (less on slower speeds).

Turbine generator? Parang nakita ba kita (o sun dial lang!?)

September 2, 2009 I'm not a UP graduate, pero kung minsan pumapasyal pasyal na din ako dun dahil sa friends ko.. Nitong huli lang a...